PFAS Fire Training Ground Water Treatment, Australian Defence, WA

Sector: PFAS
Location: Western Australia

3,600 L/h containerised plant reduced total PFAS from 5.5 to 0.014 ug/L with only half a pallet of dry filter waste after 16 months.

Client: Australian Defence military base with fire training simulation grounds and legacy AFFF contamination leaching from concrete pads.

Plant: containerised PFAS Water Treatment System, 3,600 L/h (86,400 L/day), single 1.5 kW centrifugal pump, drawing from a triple interceptor via floating suction.

Results: PFOS 3.80 to 0.0030 ug/L, PFOA 0.10 to 0.0007 ug/L, PFHxS 0.54 to 0.0033 ug/L, 6:2 FTS 0.16 to 0.001 ug/L, total PFAS 5.50 to 0.014 ug/L; TPH 1 ppm or less and sheen free. After 16 months the system had treated double the planned volume, stayed under the maintenance budget and produced only half a pallet of dry filters for incineration. No sludge, no wet waste.

More PFAS Case Studies

PFAS to Non-Detect at an Aviation Fire Training Ground, Darwin NT

Airservices Australia fire training ground water treated from up to 205 ug/L sum of PFAS to below 0.005 ug/L in a single 20 ft container at 0.75 to 1.5 L/s, operating since March 2022.

PFAS Dewatering for Civil Construction and Tunnelling, Townsville QLD

Newlands Civil Construction: 9,700 L/h, 23 ML over 3 months, sum of PFAS 13.1 to below 0.01 ug/L, six skids commissioned in one day.

PFAS Treatment for a Road Water Main Relocation, Stuart QLD

2,400 L/h skid hire achieving PFOS below 0.0002 ug/L for 99% species protection over six months with no breakthrough.